NSN 4130-01-152-5992
Part Details | AIR COOLER UNIT
4130-01-152-5992 A unit comprising a fin and tube heat transfer element, filters and may or may not have a motor driven fan, inclosed in a casing for the purpose of cooling and removing moisture from the air in a space where the unit is installed. It may include electric heater and/or electrostatic precipitator. Excludes units containing compressor, condenser and means for introducing air from outside sources.
Alternate Parts: 792482051, 79-2482-051, FCU62.5KW, FCU-6-2.5KW, 4130-01-152-5992, 01-152-5992, 4130011525992, 011525992
Supply Group (FSG) | NSN Assigned | NIIN | Item Name Code (INC) |
---|---|---|---|
41 | MAY 05, 1983 | 01-152-5992 | 11361 ( COOLER UNIT, AIR ) |
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 4130-01-152-5992
Part Number | Cage Code | Manufacturer |
---|---|---|
79-2482-051 | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
FCU-6-2.5KW | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
Technical Data | NSN 4130-01-152-5992
Characteristic | Specifications |
---|---|
OVERALL WIDTH | 22.500 INCHES NOMINAL |
OVERALL HEIGHT | 61.000 INCHES NOMINAL |
OVERALL DEPTH | 17.000 INCHES NOMINAL |
CASE MATERIAL | STEEL, GALVANIZED |
CASE WITH BUILT-IN CONDENSATE DRAIN PAN | INCLUDED |
NOMINAL CAPACITY IN BTU PER HOUR | 21500.0 COOLING AND 21500.0 HEATING |
HEATER WATTAGE RATING IN KILOWATTS | 2.5 |
TUBE MATERIAL | COPPER |
COIL TUBE QUANTITY | 1 |
TUBE CIRCUIT QUANTITY | 32 |
COOLING MEDIUM | CHILLED WATER |
CONNECTION TYPE | FLANGE UNION |
SUPPLY CONNECTION SIZE | 1.0 IN. OD |
RETURN CONNECTION SIZE | 1.0 IN. OD |
FAN TYPE | F ANY ACCEPTABLE |
FAN DRIVE TYPE | DIRECT |
PRIME MOVER HORSEPOWER RATING | 0.333 |
SPECIAL FEATURES | FAN COIL UNIT IS INTERCHANGEABLE WITH SPRUANCE AND KIDD CLASS DESTROYERS; DESIGNED FOR OVERHEAD MOUNTING; REVERSIBLE CONNECTIONS (LH/RH); USES 1 15-1/8 X 19-78 ALUMINUM AIR FILTER |
END ITEM IDENTIFICATION | FAN COIL UNIT |