NSN 4130-01-369-5026
Part Details | AIR COOLER UNIT
4130-01-369-5026 A unit comprising a fin and tube heat transfer element, filters and may or may not have a motor driven fan, inclosed in a casing for the purpose of cooling and removing moisture from the air in a space where the unit is installed. It may include electric heater and/or electrostatic precipitator. Excludes units containing compressor, condenser and means for introducing air from outside sources.
Alternate Parts: FCUH31.75KWLVR, FCU-H3-1.75KW-LVR, FCUH3 LVR1.75KW, FCU-H3 LVR-1.75KW, FCUH3LVR 1.75KW RH, FCU-H-3-LVR 1.75KW RH, FCUHLVR 1.75KW LH, FCU-H-LVR 1.75KW LH, H3 LVR1.75KW, H3 LVR-1.75KW, FCUH31.75KW LVR RH 83D4030, FCU-H-3-1.75KW- LVR RH 83D4030, FCUH31.75KW LVR LH, FCU-H-3-1.75KW- LVR LH, 4130-01-369-5026, 01-369-5026, 4130013695026, 013695026
Supply Group (FSG) | NSN Assigned | NIIN | Item Name Code (INC) |
---|---|---|---|
41 | DEC 23, 1992 | 01-369-5026 | 11361 ( COOLER UNIT, AIR ) |
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 4130-01-369-5026
Part Number | Cage Code | Manufacturer |
---|---|---|
FCU-H3-1.75KW-LVR | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
FCU-H3 LVR-1.75KW | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
FCU-H-3-LVR 1.75KW RH | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
FCU-H-LVR 1.75KW LH | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
H3 LVR-1.75KW | D9182 | ZF INDUSTRIEANTRIEBE WITTEN GMBH |
FCU-H-3-1.75KW- LVR RH 83D4030 | D9182 | ZF INDUSTRIEANTRIEBE WITTEN GMBH |
FCU-H-3-1.75KW- LVR LH | D9182 | ZF INDUSTRIEANTRIEBE WITTEN GMBH |
Technical Data | NSN 4130-01-369-5026
Characteristic | Specifications |
---|---|
OVERALL WIDTH | 27.000 INCHES NOMINAL |
OVERALL HEIGHT | 52.000 INCHES NOMINAL |
OVERALL DEPTH | 14.000 INCHES NOMINAL |
CASE MATERIAL | STEEL, GALVANIZED |
CASE WITH BUILT-IN CONDENSATE DRAIN PAN | INCLUDED |
NOMINAL CAPACITY IN BTU PER HOUR | 15280.0 COOLING AND 15280.0 HEATING |
HEATER WATTAGE RATING IN KILOWATTS | 1.75 |
TUBE MATERIAL | COPPER |
COIL TUBE QUANTITY | 1 |
TUBE CIRCUIT QUANTITY | 24 |
COOLING MEDIUM | CHILLED WATER |
CONNECTION TYPE | FLANGE UNION |
SUPPLY CONNECTION SIZE | .625 IN OD |
RETURN CONNECTION SIZE | .625 IN OD |
FAN TYPE | F ANY ACCEPTABLE |
FAN DRIVE TYPE | DIRECT |
OPERATING SPEED AT RATED CAPACITY IN RPM | 1800.0 |
SPECIAL FEATURES | MIL-A-24775; REVERSABLE CONNECTIONS (LH/RH), HIGH IMPACT SHOCK AND VIBRATION RESISTANCE; HAS LVR (LOW VOLTAGE RELEASE) CAPABILITY |
END ITEM IDENTIFICATION | FAN COIL UNIT |