NSN 4140-01-351-3168

Part Details | CENTRIFUGAL FAN

4140-01-351-3168 A nonpositive displacement mechanical device having a centrifugal fan impeller inclosed within a housing. It is designed to move air or gas over a wide range of volumes and pressures. The air or gas is drawn in axially and discharged radially or drawn in radially and discharged axially by centrifugal force through an outlet in the housing.

Alternate Parts: MILF19004, MIL-F-19004, CC12A4W6CWNM, CC1/2A4W6CW-NM, R112658 CD3560VM, R1-12658 CD-3560VM, MILF19004VM, MIL-F-19004VM, CC12A4W6CWNMVM, CC1/2A4W6CW-NMVM, R112658 CD3560, R1-12658 CD-3560, 4140-01-351-3168, 01-351-3168, 4140013513168, 013513168

Supply Group (FSG) NSN Assigned NIIN Item Name Code (INC)
41JAN 05, 199201-351-316804254 ( FAN, CENTRIFUGAL )
REFERENCE DRAWINGS & PICTURES

FIXED, RECTANGULAR OUTLETS

Cross Reference | NSN 4140-01-351-3168
Part Number Cage Code Manufacturer
MIL-F-1900481349MILITARY SPECIFICATIONSPROMULGATED BY MILITARY
CC1/2A4W6CW-NM81349MILITARY SPECIFICATIONSPROMULGATED BY MILITARY
R1-12658 CD-3560VM03950NAVAL INVENTORY CONTROL POINTMECHANICSBURG
MIL-F-19004VM03950NAVAL INVENTORY CONTROL POINTMECHANICSBURG
CC1/2A4W6CW-NMVM03950NAVAL INVENTORY CONTROL POINTMECHANICSBURG
R1-12658 CD-356009519NEW PHILADELPHIA FAN COBUFFALO FORGE MARINE FANS
Technical Data | NSN 4140-01-351-3168
Characteristic Specifications
STYLE DESIGNATOR FIXED, RECTANGULAR OUTLETS
LENGTH22.906 INCHES NOMINAL
OUTLET INSIDE WIDTH4.188 INCHES NOMINAL
OUTLET INSIDE HEIGHT11.312 INCHES NOMINAL
ROTATION DIRECTION FOR WHICH DESIGNED CLOCKWISE
PRIME MOVER TYPE ELECTRIC MOTOR
PRIME MOVER DRIVE SHAFT BEARING TYPE BALL
INCLOSURE TYPE FULLY INCLOSED
AMBIENT TEMP AT FULL RATED POWER149.0 DEG FAHRENHEIT
PRIME MOVER POWER RATING0.750 HORSEPOWER
OPERATING SPEED AT RATED CAPACITY IN RPM1800.0
VOLTAGE IN VOLTS AND CURRENT TYPE440.0 AC
PHASE THREE
FREQUENCY IN HERTZ60.0
AIR FLOW RATE400.0 CUBIC FEET PER MINUTE NOMINAL
STATIC PRESSURE AT SPECIFIED AIR FLOW RATE2.5 INCHES OF WATER
ENVIRONMENTAL PROTECTION SPRAY TIGHT
OUTLET LOCATION TOP
DISCHARGE DIRECTION HORIZONTAL
SPECIAL FEATURESMAGNETIC PERMEABILITY SHALL NOT EXCEED 2.0 AFTER FABRICATION
NONDEFINITIVE SPEC/STD DATACC TYPE
CRITICALITY CODE JUSTIFICATIONFEAT