Part Details | MOTOR STARTER

6110-01-164-3720 A device primarily designed to control the supply circuit(s) of a motor in order to accelerate the motor from rest to normal speed. Includes manual starters with overload protection and manual, automatic or semiautomatic starters consisting of combinations of items such as relays, resistors, switches, circuit breakers, and the like. Excludes RELAY-SWITCH; CIRCUIT BREAKER; SWITCH (as modified) and RELAY (as modified). For devices, which in addition to starting and stopping, reverse, select and/or regulate the speed of a motor, see CONTROLLER (as modified).

Alternate Parts: 157B2182G1S2, 6110-01-164-3720, 01-164-3720, 6110011643720, 011643720

Supply Group (FSG) NSN Assigned NIIN Item Name Code (INC)
61OCT 15, 198301-164-372000905 ( STARTER, MOTOR )
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 6110-01-164-3720
Part Number Cage Code Manufacturer
157B2182G1S202989GENERAL ELECTRIC COGE DRIVE SYSTEMS
Technical Data | NSN 6110-01-164-3720
Characteristic Specifications
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION STANDARDS DESIGN DESIGNED PER NEMA STD
SIZE DESIGNATOR4
OPERATING VOLTAGE CHARACTERISTIC REDUCED
VOLTAGE REDUCTION METHOD AUTOTRANSFORMER
FULL VOLTAGE RESTORING METHOD TIME LIMIT ACCELERATION
AC VOLTAGE RATING440.0 VOLTS NOMINAL
FREQUENCY RATING60.0 HERTZ NOMINAL
PHASE THREE
HORSEPOWER RATING100.000
FEATURES PROVIDED CIRCUIT PROTECTION FUSE
FUSE ACCOMMODATION QUANTITYA2$$A2
FUSE CURRENT RATING IN AMPSB3.0$$B10.0
CONTROL TYPE LOCAL
ACTUATION METHOD MAGNETIC
ACTUATOR VOLTAGE115.0 AC
FREQUENCY IN HERTZ60.0
PERFORMANCE TYPE AUTOMATIC AND MANUAL
LOAD PROTECTION TYPE OVERLOAD
DUTY CYCLE CONTINUOUS
AMBIENT TEMP50.0 DEG CELSIUS
SPEED ADJUSTMENTS 0 TO FULL SPEED
HAZARDOUS LOCATIONS/ENVIRONMENTAL PROTECTION DRIPPROOF
INCLOSURE FEATURE DRIPPROOF
OVERALL WIDTH51.375 INCHES NOMINAL
OVERALL LENGTH20.390 INCHES NOMINAL
OVERALL HEIGHT13.000 INCHES NOMINAL
MOUNTING CONFIGURATIONEIGHT 21/32 IN. DIA HOLES; RECTANGULAR PATTERN; TWO HORIZONTAL ROWS OF 4 EA; 18-3/8 IN. CL TO CL OF ROWS; C TO C SPACING OF HOLES FROM RIGHT; 12-1/4 IN.; 13-3/8 IN.; 21 IN.
SWITCH FUNCTIONAL POSITIONS RUN AND START