NSN 6350-01-469-3167

Part Details | OPAQUE PARTICLE SENSOR

6350-01-469-3167 A device designed to detect the presence of predetermined amounts of smoke, dust, and the like, within the measuring area. The presence of any of these substances causes a change in the output signal of the device, which relays a warning message back to a central panel. The device itself does not provide any audible or visible output, or analyze chemical content. Excludes ALARM, SMOKE, AUTOMATIC.

Alternate Parts: 500095112C, 500-095112C, 500095026, 500-095026, 500095112C, 500-095112C, 6350-01-469-3167, 01-469-3167, 6350014693167, 014693167

Supply Group (FSG) NSN Assigned NIIN Item Name Code (INC)
63NOV 10, 199901-469-316737790 ( SENSOR, OPAQUE PARTICLE )
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 6350-01-469-3167
Part Number Cage Code Manufacturer
500-095112C0A0E0CERBERUS PYROTRONICS INC
500-0950260A0E0CERBERUS PYROTRONICS INC
500-095112C1HLQ3SIEMENS INDUSTRY INC.DIV CORPORATE HEADQUARTERS
Technical Data | NSN 6350-01-469-3167
Characteristic Specifications
MEDIA DETECTED SMOKE
ELECTRICAL POWER SOURCE RELATIONSHIP OPERATING
DESIGN TYPE NONTRIPOD MOUNTING
OVERALL WIDTH2.300 INCHES NOMINAL
OVERALL DIAMETER6.000 INCHES NOMINAL
SPECIAL FEATURESPLUG-IN, 2 WIRE, MULTI-SENSOR DETECTOR, PHOTOELECTRIC (FOR SMOKE) AND THERMAL SENSING UNITS; COMPATIBLE WITH MXL FAMILY OF CONTROL PANELS; ELECTRICALLY COMPATIBLE WITH EXISTING MXL DETECTOR ACCESSORIES; REQUIRES P/N 500-095687, MODEL DB-11C (MOUNTING BASE, SERIES 11) FOR SOME OLDER MXL SYSTEMS; DUST RESISTANT; FIELD CLEANABLE PHOTO CHAMBER; SOLID STATE, NON-MECHANICAL THERMAL SENSOR; MICRO PROCESSOR BASED ELECTRONICS; MODEL FPI-32 PROGRAMMER/TESTER (NOT INCLUDED) USED TO ELECTRONICALLY PROGRAM AND VERIFY DETECTORS ADDRESS; FPI-32 ALLOWS USER TO CHANGE DEVICE FROM FP-11C TO OLDER DETECTOR ID WITHOUT HAVING TO REPROGRAM CONTROL PANEL; MULTI-COLOR LED FLASHES GREEN FOR NORMAL CONDITION, AMBER FOR DETECTOR FAULT, AND RED, WHEN INSTRUCTED BY PANEL, FOR ALARM CONDITION; CAPABLE OF BI-DIRECTIONAL COMMUNICATION WITH CONTROL PANEL; CURRENT REQUIRES 0.750 AMPS; PLUS 32 TO PLUS 100 DEG. F OPERATING TEMP; 0 TO 93 PERCENT HUMIDITY NON-CONDENSING; ULC LISTED
FUNCTIONAL DESCRIPTIONFIRE DETECTION UNIT, CHECKS FOR SMOKE AND THERMAL VARIATIONS, RELAYING DATA TO CONTROL PANEL
TYPE/MODEL DESIGNATIONFP-11C