NSN 6625-00-542-1331

Part Details | INSULATION BREAKDOWN TEST SET

6625-00-542-1331 A test set primarily designed to detect and indicate insulation breakdown in electric motors, transformers, and the like, at specific test voltages. See also TEST SET, ARMATURE; and OHMMETER.

Alternate Parts: 22001M0DEL1, ANGSM6, SMD349276, SM-D-349276, 6625-00-542-1331, 00-542-1331, 6625005421331, 005421331

Supply Group (FSG) NSN Assigned NIIN Item Name Code (INC)
66JAN 01, 196100-542-133116408 ( TEST SET, INSULATION BREAKDOWN )
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 6625-00-542-1331
Part Number Cage Code Manufacturer
22001M0DEL107239AVO INTL
ANGSM680058JOINT ELECTRONICS TYPE DESIGNATIONSYSTEM
SM-D-34927680063US ARMY COMMUNICATIONS &ELECTRONICS MATERIEL READINESS
Technical Data | NSN 6625-00-542-1331
Characteristic Specifications
OUTPUT CURRENT TYPE DC
OUTPUT VOLTAGE RATING400.000 VOLTS MINIMUM AND 500.000 VOLTS MAXIMUM
INSTALLATION DESIGN PORTABLE
LEAKAGE INDICATOR TYPE METER
METER QUANTITY2
METER TYPE AMMETER AND VOLTMETER
SCALE RANGE+0.0 TO +40.0 KILOVOLTS AND +0.0 TO +50.0 MICROAMPS
AC VOLTAGE RATING115.0 VOLTS NOMINAL
FREQUENCY RATING60.0 HERTZ NOMINAL
PHASE SINGLE
OVERALL LENGTH20.000 INCHES NOMINAL
OVERALL WIDTH13.500 INCHES NOMINAL
OVERALL HEIGHT19.500 INCHES NOMINAL
SPECIAL FEATURESCIRCUIT BREAKER OVERLOAD PROTECTIION W/SPARK GAP AND NEON LAMPS TO PROTECT METER;AMMETERS HAS MULTIPLIERS OF 1,10,100 AND 1000 TO INCREASE RANGE TO50,000 UA,VOLTAGE DOUBLER TYPE CIRCUITW/HIGH VOLTAGE SECTION IMMERSED IN OIL;EITHER PLUS OR MINUS OUTPUT TERMINAL MAY BE CONNECTED TO GUARD TO FORM/COLDGUARD CIRCUIT;INCL 1 TEST SET NO. TS-928/U,1 CABLE ASSEMBLY,POWER,ELECTRICAL,50 FT LG AND 1 LEAD ELECTRICAL 5 FT LG